TrueAlarm heat detectors are self-restoring and provide rate compensated, fixed temperature sensing, selectable with or without rate-of-rise temperature sensing. Due to its small thermal mass, the detector accurately and quickly measures the local temperature for analysis at the CIE Rate-of-rise temperature detection is selectable for either 8.3°C or 11.1°C per minute. Fixed temperature sensing is independent of rate-of-rise sensing and programmable to operate at 57.2°C or 68°C. In a slow developing fire, the temperature may not increase rapidly enough to operate the rate-of-rise feature, however an alarm will be initiated when the temperature reaches its rated fixed temp setting.

Technical Details

Width (mm):
100.0
Height (mm):
60.0
Alarm Current (max):
10mA
Ambient Temperature:
0 to +50°C
Dimensions:
L100 x W100 x H60mm
External Output Drive (max):
5mA
Length (mm):
100
Operating Voltage:
24 to 40Vdc*
Pack Quantity:
1.0
Quiescent Current (max):
400A
Relative Humidity:
10% to 95% (n/cond)
Single Units:
Yes
Weight:
100g